Answer EKG Question 36
Q36. With reference to Boiler water tests carried out on board:
A. Discuss the possible reasons for the following changes in boiler water test results, and state what actions should be taken in each case;
1. Reduction in total dissolved solids and chemical reserves.
2. Reduction in phosphate reserve, with increase in chlorides and total dissolved solids;
3. Reduction in alkalinity reserve only.
4. Increase in oxygen levels only.
A. Discuss the possible reasons for the following changes in boiler water test results, and state what actions should be taken in each case;
1. Reduction in total dissolved solids and chemical reserves.
2. Reduction in phosphate reserve, with increase in chlorides and total dissolved solids;
3. Reduction in alkalinity reserve only.
4. Increase in oxygen levels only.
B.
State why the complete results of boiler water tests are logged or
entered into a data retrieval system rather than a note being made of
any particular result which may be outside set limits.
Answer: (A) Possible reasons and actions:-
1.
T.D.S and Chemical reserve in the boiler can be reduced because of the
water leakage from leaking tubes or because of any other source of water
leakage. Actions to be taken:- water leakage from tube can be seen as
white smoke from the boiler funnel along with frequent level drop in
boiler drums which leads to frequent requirement to refill the cascade
tank. Also the boiler may fail to fulfill the required demand of steam.
Trace the leakage and repair the same, carry out adequate chemical
treatment.
2.
Reduction in phosphate reserve, with increase in chloride and T.D.S can
take place if the sea water leakage in the system. Actions to be
taken:- sea water can enter in the system through condenser system.
Trace the source of sea water leakage in the system.
3.
Reduction in alkalinity reserve only takes place when lube oil with
high alkalinity leaks in. Actions to be taken:- lube oil can enter
through the purifier feed heater. same needed to be traced and
rectified.
4.
Increase in oxygen levels only takes place when ingress of air takes
place. where de-aeration system uses vacuum principle it is more prone
to air ingress. Actions to be taken:- Trace the source of air ingress
and it can be from defective flanges, gaskets, uncovered cascade tank or
cracked valve bonnets. Maintain temperature of hot-well and check for
the ventilation of the from de-aerator.
(B)
By logging the boiler water test results we can follow the gradual
trend of value deviation within the normal range. This record is helpful
in scheduling the chemical treatment.