Solution Electrical Numerical 20

Numerical 20: Two 10 MVA 3 phase Alternator operate in parallel to supply at 0.8 power factor with lagging load of 15 MVA. If the output of one Alternator is 8 MVA at 0.9 lagging. 1. Calculate the output of second Alternator. 2. Calculate the value of Power factor of second Alternator.
Solution: we need to calculate active and reactive components for the further calculation: 

Parallel operation:
Load = 15 MWA
p.f = cosф = 0.8
thus, sinф = 0.6
Active load =  15 x 0.8 = 12 MW
Reactive load = 15 x 0.6 = 9 MVAr

Alternator One:
Load  = 8 MVA
p.f = cosф = 0.9
thus, sinф = 0.4358
Active load = 8 x 0.9 = 7.2 MW
Reactive load = 8 x 0.4358 = 3.4864 MVAr

Alternator Two:
Active load = 12 - 7.2 = 4.8 MW
Reactive load = 9 - 3.4864=5.5136 MVAr
$\displaystyle \mathrm{Load = \sqrt{Active\ load ^2 +\ Reactive\ load^2 }}$ 
$\displaystyle \mathrm{Load = \sqrt{4.8 ^2 +\ 5.5136^2 }}$ 
Load = 7.317 MVA
$\displaystyle \mathrm{cos\phi = \frac{MW}{MVA}\ =\ \frac{4.8}{7.317}\ =\ 0.656}$

Comments